The LEVELIS LPU-4XX-P programmable display unit
The LEVELIS LPU-4XX-P programmable display unit is used to visualize physical quantities such as fluid level or flow rate, the magnitudes of which are expressed by means of a signal current 0/4 to 20mA. The data are displayed in linear, quadratic, square-root or other user-defined modes. The display unit is designed to be fitted into an operator panel. The unit parameters can be set by buttons on the front side.
The LEVELIS LPU-4XX-P display unit: main features
- 4-digit LED display
- input signal 0/ 4 to 20mA
- 2 or 4 relay outputs
- operator-panel mounting
- button parameter setting
- RS 485/ Modbus communication interface
Technical parameters - LEVELIS LPU-4XX-P |
|
design version | panel mounted, rear terminal strip |
power source | 85 to 260V AC/DC (50 to 60Hz) 16 to 35V AC (50 to 60Hz) 19 to 50V DC |
power requirement | max. 4.5V A/4.5W |
display unit | 4-digit LED, character height 20mm |
input | 0/4 to 20mA, overload protection |
display range | -999 to 9999, decimal point |
measurement accuracy | ±0.25% ±1 digit |
relay output | 2 or 4 relays 1A/250V AC |
current output (2-relay version only) | insulated, signal range 0 to 24mA |
output for external power supply | 24VDC +5%, -10% max. 100mA |
ambient temperature | 0°C to 50°C |
communication interface | RS 485, Modbus RTU |
protection class | front side IP40 |
Download |
|
Catalogues | |
![]() |
|
Manuals | |
![]() |